New (48*48mm) Digital Temperature Humidity Controller Thermostat Humidity Control TDK0348LA with 3m wire Free shipping

New (48*48mm) Digital Temperature Humidity Controller Thermostat Humidity Control TDK0348LA with 3m wire Free shipping
  • Продавецguaranteedautos.us
  • Список ценUS $31.99piece
  • Продажная ценаUS $31.99piece
  • ДоставкаБесплатная доставка
  • Рейтинги3,7 (486)

Oписание продукта

product description
Control range:1%RH-99%RH

Load power:10A/AC220V

Measurement range:-20℃~80℃

Humidity range:1%RH-99%RH

Measurement error:±3%RH(environment temperature at 25℃)

Temperature precision:1℃ Humidity precision:1%RH

Display accuracy:1%RH

Power Supply:DC12V//220V(Choose)

Output type:10A relay output probe type

Temperature: NTC precision ±1℃

Humidity:resistance type sensor precision ±3℃

Dimension:90*60*26.5mm(L*W*H)

Temperature control object:one channel temperature(heating and refrigeration ventilator)

Or humidity(Dehumidify or humidify electrical appliance)

Probe line length:standard 1.5m

Permanent memory of parameter:set the all parameter with permanent memory

Power failure at the operation time:run after the power supply.

Working environment: temperature 0-55℃ humidity90%RH without condensation

Menu code description:

Code

Code description

Setting range

Factory

Unit

HC

Humidification/ dehumidification

H/C

C

Without

D

Humidity return difference

1-30

5

%RH

LS

Humidity lower limit

1

5

%RH

HS

Humidity limit

99

95

%RH

CA

Humidity correction

-10-10

0

%RH

PT

Delay start

0-10

1

Minutes

LS

AL-L

-20

 

HS

AL-H

80

 

CA

Temperature correction

-10-10

 

 

PT

Delay start

0-10

 

Minute

Humidity control setting:Press Set keyboard one time,press three second enter into setting menu after humidity display flashing,it will display code HC.Press "▲ "keyboard or "▼"keyboard can cyclical selection HC-CP-PU-CA-HP parameter code.Please press Set keyboard if you need enter into a code,press "▲ "keyboard or "▼"keyboard to modify the required numerical for five seconds then return automatically.

Press "SET" keyboard twice enter into setting menu after temperature display flashing,and display code HC,press "▲ "keyboard or "▼"keyboard can cyclical selection HC-CP-PU-CA-HP

parameter code,please press "SET " keyboard if you need enter into one code ,press "▲ "keyboard or "▼"keyboard to modify the required numerical for five seconds then return automatically.

Dehumidification control: The way of mode control (code HC) it will be dehumidification control when setting as C.For example,set the humidity control value as 50% RH and humidity difference as 5%,relay start output,When environment humidity value ≤setting humidity value(50%RH),relay close output.

Damping control:The way of humidity control  (code HC) ,set H as damping mode,for example,set the humidity control value as 50%RH and humidity difference as 5%RH. When temperature humidity value ≤setting value(50%RH)-difference/(5%RH) ,relay start output.when temperature humidity ≥setting value(50%RH),relay stop output.

HC:mode selection,H means humidifying mode,C means dehumidificatio mode.

D:return difference, start the humidify when in the humidifying mode=displaying humidity-return difference.start the humidify when in dehumidification mode=displaying humidity + return difference.

PU:Delay to start.when relay stop output and start timing.the interval time of next boot must greater than delay start time to avoid start frequently.

HP:Humidity upper limit alarm:when humidity exceed upper limit alarm,digital tube displaying "-H-",humidity lower than alarm setting value it will return back from alarm automatically.

LS;Humidity lower limit alarm:When humidity exceed lower limit,digital tube display"-L-",humidity higher than alarm setting value it will return back from alarm automatically.

CA:Humidity correction:Humidity correction value plus displaying value.For example:humidity display 50% RH correction humidity increase 5% RH,then display humidity will be 55%RH.

Heating mode:Mode control way (code HC) set as H ,it is heating mode.For example,set control heating value as 35℃,temperature return difference is 2°.when environment humidity value ≥setting temperature value(35℃)-return difference(2 ℃),relay start output.when humidity value≤setting humidity value (35℃),relay close output.

Cooling control:The way of mode control ,set (HC code) as C ,it is cooling mode.For example,set cooling as 35 ℃ and temperature return difference as 2 ℃.When environment value ≥ setting temperature value (35℃)+return difference(2℃),relay start output:when environment humidity value≤setting humidity value(35 ℃),relay stop output.

HC:Mode selection,C means cooling mode,H means heating mode.

D:return difference,start temperature when in heating mode= displaying temperature"-return difference.Start temperature when in cooling mode=displaying temperature+return difference.

PU:Delay to start,When relay stop output and start timing,the interval of time must greater than delay start time to avoid start frequently.HP:temperature upper limit alarm:when temperature exceed upper limit alarm,digital tube display"HHH",temperature lower than alarm setting it will return back from alarm automatically.

LS:temperature lower limit alarm:when temperature exceed than lower limit alarm,digital tube display "LLL",temperature higher than alarm setting it will return back from alarm automatically.

CA temperature correction:Humidity correction value plus display humidity value,for example:humidity displaying 35℃ ,correction humidity increase 5℃,then temperature should be 35℃.

Reset:Press left up and down keyboard until screen displaying 888,then it will coma back to factory reset.

8909022567_6187782328946113767_618778232